Three-Phase Power

Introduction to Three-Phase Power

The means of generation, transfer, and consumption of AC power that we have discussed so far is known as single-phase power. If not already familiar with three-phase power, you will be surprised to learn that single-phase power is not the main way that power is transferred in the electrical grid. In a single-phase system, a sinusoidal voltage v(t)v(t) is generated between a set of two power lines such that power is transferred to loads placed across those lines (in parallel). This is illustrated by Figure 1(a). As we learned in the previous chapter, the power delivered by a single-phase circuit oscillates sinusoidally with time, which can be impractical.

On the other hand, three-phase power, sometimes abbreviated 3ϕ3 \phi, is a way of transmitting power for which the power delivered is constant over time. Steady power is advantageous for heavy industrial loads, such as large electric motors, and for long-distance transmission. This is one reason why three-phase power is carried by the grid’s transmission lines, besides the fact that three-phase power can reduce the amount of conductor material needed and thus results in reduced infrastructure costs.

A three-phase circuit has three voltage lines, each of which carries a sinusoidally oscillating voltage. The three voltages are called phase voltages and are denoted va(t)v_a(t), vb(t)v_b(t), and vc(t)v_c(t). The three voltage sinusoids are of equal magnitude ∣V∣|V|, but their phase angles are one third of a cycle (2π/32 \pi / 3 radians) apart, meaning that the three voltage sinusoids sum to zero at any given time. The three phase voltages can be represented by phasors as in Figure 2.

The generators that supply the phase voltages (and thus power the circuit) are called three-phase generators, and the loads that are powered by the circuit are called three-phase loads. Each of these generators and loads is connected to all three lines. This is illustrated by Figure 1(b). Each load actually consists of three impedances. If a given load’s three impedances are of equal value (ZZ), then the load is called a balanced three-phase load. A three-phase circuit in which all loads are balanced is called a balanced three-phase circuit.

For a balanced load, the fact that the voltage sinusoids sum to zero also means that the sinusoidal currents through the three impedances sum to zero. In other words, the three currents cancel out. Thus, no extra line is required to carry current back to the generator(s), as is required in a single-phase circuit. This is why a balanced three-phase circuit can transfer the same amount of power as a single-phase circuit, but with less conductor material. An unbalanced three-phase circuit, on the other hand, requires a fourth neutral line to which each unbalanced load connects.

Single- and three-phase systems.

Figure 1:Single- and three-phase systems.

Three-phase voltage phasors.

Figure 2:Three-phase voltage phasors.

Comparison of n-Phase Circuits

Circuits with a number of phases other than one or three are possible. Circuits with more than one phase are known as polyphase systems. But why is three-phase power more common than other polyphase systems, and more common than even single-phase systems? Why not two-phase power, or four? This section will compare circuits with an arbitrary number of phases nn. We will determine the advantages and disadvantages of circuits with different numbers of phases. We will assume balanced three-phase loads with, for simplicity, impedance value RR. However, the conclusions would be the same for an arbitrary impedance ZZ.

Consider a circuit with a single phase aa, such as that shown in Figure 3(a). It has one impedance Ra=RR_a = R, supplied by one phase voltage:

va(t)=∣V∣cos⁡ωtv_a(t) = |V| \cos \omega t

Recall the instantaneous power delivered over time in a single-phase circuit from Chapter 5. In a single-phase circuit, the total power p tot.(t)p_{\, \text{tot.}}(t) delivered in the circuit is just the power pa(t)p_a(t) delivered to impedance RaR_a, the time-average of which is pˉ tot.=∣V∣2/ 2R\bar{p}_{\, \text{tot.}} = |V|^2 / \, 2 R.

p tot.(t)=pa(t)=∣V∣2R=∣V∣2Rcos⁡2ωt= 12∣V∣2R⏟pˉ tot.+12∣V∣2Rcos⁡2ωtp_{\, \text{tot.}}(t) = p_a(t) = \frac{|V|^2}{R} = \frac{|V|^2}{R} \cos^2 \omega t = \underbrace{\, \frac{1}{2} \frac{|V|^2}{R}}_{\bar{p}_{\, \text{tot.}}} + \frac{1}{2} \frac{|V|^2}{R} \cos 2 \omega t

Similarly, the sum of the phase currents i tot.(t)i_{\, \text{tot.}}(t) is just the current ia(t)i_a(t) delivered through impedance RaR_a, as follows:

i tot.(t)=ia(t)=∣V∣Rcos⁡ωti_{\, \text{tot.}}(t) = i_a(t) = \frac{|V|}{R} \cos \omega t

Of course, the sum of the phase currents is nonzero (except where it crosses the ωt\omega t-axis) and we need a ‘return’ line (the neutral line) connected to the same 0-V potential as voltage source vav_a. While these conclusions may seem obvious for a single-phase circuit, we will see that they do not necessarily apply to higher-phase circuits.

In a two-phase circuit such as in Figure 3(b), we have two imped­ances, Ra=Rb=RR_a = R_b = R. The impedances’ respective voltages are va(t)v_a(t) and vb(t)v_b(t), whose magnitudes are both ∣V∣|V| and whose phases are π/2\pi / 2 radians out-of-phase relative to each other:

va(t)=∣V∣cos⁡ωtvb(t)=∣V∣cos⁡(ωt+π/2)\begin{aligned} & v_a(t) = |V| \cos \omega t \\ & v_b(t) = |V| \cos (\omega t + \pi / 2) \end{aligned}

The total power delivered in the two-phase circuit is the sum of power delivered to both loads, as follows. Note that it is no longer sinusoidal, as in was in the single-phase circuit, but constant. In fact, the time-average total power delivered by any circuit with n≥2n \geq 2 phases is always constant, making such circuits strong contenders for being able to deliver a steady supply of total power in a power system.

p tot.(t)=pa(t)+pb(t)=Va2+Vb2R=(∣V∣cos⁡ωt)2+(∣V∣cos⁡ ⁣(ωt+π2))2RApply Pythagorean identity, sin⁡2x+cos⁡2x=1:=∣V∣2((cos⁡ωt)2+(−sin⁡ωt)2)R=∣V∣2R⏟pˉ tot.\begin{aligned} p_{\, \text{tot.}}(t) & = p_a(t) + p_b(t) \\ & = \frac{V_a^2 + V_b^2}{R} \\ & = \frac{(|V| \cos \omega t)^2 + \left( |V| \cos \! \left( \omega t + \frac{\pi}{2} \right) \right)^2}{R} \\ & \text{Apply Pythagorean identity, $\sin^2 x + \cos^2 x = 1$:} \\ & = \frac{|V|^2 ((\cos \omega t)^2 + (- \sin \omega t)^2)}{R} \\ & = \underbrace{\frac{|V|^2}{R}}_{\bar{p}_{\, \text{tot.}}} \end{aligned}

Just as in the single-phase circuit, the sum of the phase currents in the two-phase circuit is nonzero and a neutral line is indeed needed:

i tot.(t)=ia(t)+ib(t)=∣V∣cos⁡ωt+∣V∣cos⁡ ⁣(ωt+π2)=2 ∣V∣Rcos⁡ ⁣(ωt+π4)\begin{aligned} i_{\, \text{tot.}}(t) & = i_a(t) + i_b(t) \\ & = |V| \cos \omega t + |V| \cos \! \left( \omega t + \frac{\pi}{2} \right) = \sqrt{2} \, \frac{|V|}{R} \cos \! \left( \omega t + \frac{\pi}{4} \right) \end{aligned}

In a three-phase circuit such as in Figure 3(c), the three phase voltages are 2π/32 \pi / 3 radians out-of-phase relative to each other:

va(t)=∣V∣cos⁡ωtvb(t)=∣V∣cos⁡(ωt+2π/3)vc(t)=∣V∣cos⁡(ωt−2π/3)\begin{aligned} & v_a(t) = |V| \cos \omega t \\ & v_b(t) = |V| \cos (\omega t + 2 \pi / 3) \\ & v_c(t) = |V| \cos (\omega t - 2 \pi / 3) \end{aligned}

Just as in the two-phase circuit, the total power delivered in the three-phase circuit is constant:

p tot.(t)=pa(t)+pb(t)+pc(t)= 32∣V∣2R⏟pˉ tot.p_{\, \text{tot.}}(t) = p_a(t) + p_b(t) + p_c(t) = \underbrace{\, \frac{3}{2} \frac{|V|^2}{R}}_{\bar{p}_{\, \text{tot.}}}

However, unlike the single- and two-phase circuits, the sum of the phase currents in the three-phase circuit is zero at all times (as long as the loads are balanced). Thus, no neutral line is needed. In fact, no neutral line is needed for any circuit with n≥3n \geq 3 phases. This means that a three-phase circuit can deliver 3 times as much power as a single-phase circuit using only 1.5 times as many lines and only 1.5 times as much conductor material.

Indeed, in circuits with more than three phases, such as in Figure 3 (d) and (e), the time-average total power delivered is constant and no neutral line is needed—the same as for a three-phase circuit. Circuits with n>3n > 3 phases have no advantage over three-phase circuits and are avoided because they need more conductors that would have to be installed and maintained in the power system (even if they need the same number of conductors per unit power). Thus, three-phase power is the clear winner out of the candidates tabulated in Table 1.

Table 1:Summary of circuits with different numbers of phases, in terms of the minimum number of lines needed, whether the total power is sinusoidal or constant, the time-average total power, and the time-average total power per line.

nnMin. # of linesTotal power, p tot.(t)p_{\, \text{tot.}}(t)Avg. total power, pˉ tot.\bar{p}_{\, \text{tot.}}Avg. total power per line
12Sinusoidal (Eq. (2))=∣V∣2/ 2R= |V|^2 / \, 2 R=∣V∣2/ 4R= |V|^2 / \, 4 R
23Constant=∣V∣2/R= |V|^2 / R=∣V∣2/ 3R= |V|^2 / \, 3 R
33Constant=3∣V∣2/ 2R= 3 |V|^2 / \, 2 R=∣V∣2/ 2R= |V|^2 / \, 2 R
44Constant=2∣V∣2/R= 2 |V|^2 / R=∣V∣2/ 2R= |V|^2 / \, 2 R
Any n≥3n \geq 3nnConstant=n∣V∣2/ 2R= n |V|^2 / \, 2 R=∣V∣2/ 2R= |V|^2 / \, 2 R
Comparison of n-phase systems.

Figure 3:Comparison of nn-phase systems.

Wye Versus Delta Configurations

So far, we have assumed three-phase generators and loads to be in the Y\mathrm{Y} configuration (pronounced, and often written as, “wye”). Also called the “star” configuration, the wye configuration includes a 0-V neutral node which is normally grounded and will be denoted nn. Each of the three-phase lines aa, bb, and cc are indirectly connected to nn. In a three-phase generator following the wye configuration, each of the three lines is connected to node nn through a voltage source viv_i, resulting in the three phase voltages vi(t)v_i(t). In a wye-configured three-phase load, each of the three lines is connected to node nn through an impedance ZZ. If the load is unbalanced, a fourth, neutral line is required to carry extra current at node nn of the load back to node nn of the generator. The different cases are illustrated in Figure 4.

There is a second three-phase configuration called Δ\Delta, or delta. In the delta configuration, components—whether voltage sources or imped­ances—are not connected between each line and neutral. Instead, components are connected across each pair of lines: (a,b)(a, b), (b,c)(b, c), and (c,a)(c, a). There is no node nn and no possibility of a neutral line, so loads following the delta configuration must be balanced. The voltage across each component is the difference between the voltages of the two lines to which it is connected, e.g., vba(t)=vb(t)−va(t)v_{ba}(t) = v_b(t) - v_a(t). The magnitude of the voltage across each component is 3∣V∣\sqrt{3} |V|, or 3\sqrt{3} times as much that of a wye-connected counterpart.

Both wye- and delta-configured generators and loads can be connected to the same three-phase circuit.

Wye- and delta-configured sources and impedances.

Figure 4:Wye- and delta-configured sources and impedances.

What about transformers? A transformer is like a generator and a load, simultaneously. A regular transformer has two windings—prim­ary and secondary. A three-phase transformer typically has two sets of three windings apiece. If we’re talking about a transformer in a grid substation, whose role is to step down voltage levels, then the primary set of windings acts as a load on the high-voltage side, and the secondary set acts as a generator for the low-voltage side. A three-phase transformer can have two wye-configured sets of windings, two delta-configured sets of windings, or one wye-configured set and one delta-configured set, as illustrated in Figure 5. As can be seen in Figure 5, a three-phase transformer can be constructed from three single-phase transformers.

Three-phase transformer configurations.

Figure 5:Three-phase transformer configurations.

In a delta-wye transformer, 3\sqrt{3} times the phase voltage on the primary side is converted to the phase voltage on the secondary side. In a wye-delta transformer, the inverse is true: the primary side’s phase voltage is converted to 3\sqrt{3} times the secondary side’s phase voltage. Thus, even with the same number of primary windings as secondary windings, a delta-wye or wye-delta transformer steps voltage up or down, respectively, by a factor of 3≈1.73\sqrt{3} \approx 1.73.

A transformer provides isolation between the primary and secondary sides, allowing a neutral line to exist on a wye-configured set of windings while being absent on the other set of windings, as shown in Figure 5(a) and (c).

Three-Phase Power in the Grid

Most appliances—even high-power appliances like ovens, clothes dryers, and many residential EV chargers—use single-phase power. Thus, most residential and commercial buildings are supplied with single-phase power. How is this possible when the rest of the grid is three-phase? In reality, a building’s single-phase supply represents one part of a larger, three-phase load formed at the distribution level of the grid. Each of these high-level three-phase loads includes the electrical supply to multiple buildings.

Efforts are made to design the topology of the grid such that the impedances between the three branches are balanced. Unbalanced impedances would mean that the lines and transformers that feed them are underutilized. However, there is only so much that can be done. The impedance on a given branch can change at the press of a button—when someone turns on their clothes dryer, for example. Thus, the wye configuration, with a neutral line, must be used.

As we move up in the distribution grid, transformers are encountered to convert between voltage levels.